研究目的
Investigating the effect of connecting two photovoltaic systems to a power line with a distributed load in terms of power losses and determining the optimal power and places of connection of photovoltaic systems.
研究成果
The study concludes that to achieve maximum loss reduction in a uniformly distributed load supply line, two additional power sources should be used, each with a power of 0.4 of the active power consumption of loads connected to the line, and should be included at a distance of 0.4 and 0.8 of the line length from its beginning. The developed method allows for the determination of different combinations of optimal power and connection points.
研究不足
The study focuses on power supply systems to poultry farms and may not be directly applicable to other types of distributed loads without further research.
1:Experimental Design and Method Selection:
The study analyzes the effect of connecting two photovoltaic systems to a power line with a distributed load in terms of power losses. Two methods are proposed for determining the optimal power and places of connection of photovoltaic systems.
2:Sample Selection and Data Sources:
The systems of power supply to poultry farms were analyzed as the objects of research.
3:List of Experimental Equipment and Materials:
Not explicitly mentioned.
4:Experimental Procedures and Operational Workflow:
The study involves analyzing the effect of connecting photovoltaic systems to a power line and proposing methods for determining their optimal power and connection places.
5:Data Analysis Methods:
Analytical expressions for minimum electric power losses in a power line with distributed load are used, along with a developed nomogram.